Medium Voltage (up to 35kV) XLPE Insulated Power Cable
| Cross-sectional Area (mm²) | Average overall diameter (mm) | Core | Reference weight (kg/km) | Conductor Resistance 20ºC Max (Ω/km) | |
| 50 | - | 26 | 1 | 1003 | ≤0.387 |
| 70 | - | 27 | 1 | 1233 | ≤0.268 |
| 95 | - | 29 | 1 | 1520 | ≤0.193 |
| 120 | - | 30 | 1 | 1799 | ≤0.153 |
| 150 | - | 32 | 1 | 2088 | ≤0.124 |
| 185 | - | 34 | 1 | 2482 | ≤0.0991 |
| 240 | - | 36 | 1 | 3080 | ≤0.0754 |
| 300 | - | 38 | 1 | 3674 | ≤0.0601 |
| 400 | - | 41 | 1 | 4572 | ≤0.0470 |
| 500 | - | 44 | 1 | 5890 | ≤0.0366 |
| 50 | - | 52 | 3 | 3318 | ≤0.727 |
| 70 | - | 55 | 3 | 4104 | ≤0.524 |
| 95 | - | 59 | 3 | 5049 | ≤0.387 |
| 120 | - | 62 | 3 | 5937 | ≤0.268 |
| 150 | - | 66 | 3 | 6896 | ≤0.193 |
| 185 | - | 69 | 3 | 8141 | ≤0.153 |
| 240 | - | 75 | 3 | 10075 | ≤0.124 |
| 300 | - | 80 | 3 | 12004 | ≤0.0991 |
| 400 | - | 86 | 3 | 14887 | ≤0.0754 |
Description Of Medium Voltage (up to 35kV) XLPE Insulated Power Cable
Rated Temperature: 90℃
Rated Voltage: up to 26/35kV
Reference Standard: IEC60502-2
Conductor: Shaped and circular stranded copper conductors
Insulated: Insulated with Cross-linked polyethylene
Sheathed: PVC
Medium voltage (up to 35kV) XLPE insulated power cable utilize chemical cross-linking (peroxide-initiated) or physical irradiation processes to convert linear polyethylene molecules into a three-dimensional thermosetting network structure. This transformation enhances the material’s thermal stability, elevating its maximum operating temperature from 75°C (thermoplastic PE) to 90°C (short-circuit withstand up to 250°C), while retaining superior dielectric properties.
Application of Medium voltage (up to 35kV) XLPE insulated power cable:
Urban Distribution Networks: Medium-voltage connections between ring main units (RMUs) and transformers.
Industrial Power Supply: Main feeder lines in chemical plants, refineries, and corrosive environments.
Rail Transit: Power transmission for traction substations and electrified rail systems.
Renewable Energy: PV plant step-up circuits/Wind farm collector lines
Submarine Cables: XLPE insulation with lead-sheath protection for subsea power transmission (≤35 kV).